UTE FUSE PRODUCT PAGE

Dimensional Drawing| Part Number Listing| Time-Current Curves| Specifications
 
CATEGORY - ELECTRONIC
Time-Lag Low Breaking Capacity
 
SIZE: 5X20ute
Body Material:GLASS
Acting:Time Delay
Axial Leads:No
Printable Version (PDF)
 
DIMENSIONAL DRAWING:
FUSE SPECS:

Catalogue
Number
Ampere
Rating,A
Voltage,
Volt
Melting I2t,
A2Sec
Approvals
UTE.5000.5002500.525SEMCO, VDE, BSI, IMQ, UR, CSAA, CCEE
UTE.6300.6302501.151SEMCO, VDE, BSI, IMQ, UR, CSAA, CCEE
UTE.8000.8002502.240SEMCO, VDE, BSI, IMQ, UR, CSAA, CCEE
UTE0011.0002502.400SEMCO, VDE, BSI, IMQ, UR, CSAA, MITI, CCEE
UTE1.251.2502507.500SEMCO, VDE, BSI, IMQ, UR, CSAA, MITI, CCEE
UTE1.601.6002506.144SEMCO, VDE, BSI, IMQ, UR, CSAA, MITI, CCEE
UTE0022.0002508.800SEMCO, VDE, BSI, IMQ, UR, CSAA, MITI, CCEE
UTE2.502.50025015.000SEMCO, VDE, BSI, IMQ, UR, CSAA, MITI, CCEE
UTE3.153.15025029.760SEMCO, VDE, BSI, IMQ, UR, CSAA, MITI, CCEE
UTE0044.00025056.000SEMCO, VDE, BSI, IMQ, UR, CSAA, MITI, CCEE
UTE0055.00025070.000SEMCO, VDE, BSI, IMQ, UR, CSAA, MITI, CCEE
UTE6.306.300250198.400SEMCO, VDE, BSI, IMQ, UR, CSAA, CCEE
UTE0088.000250345.600VDE, UR, CSAA, MITI, CCEE
UTE01010.0002501100.000VDE, UR, CSAA, MITI, CCEE
TIME_CURRENT CURVES:
TECHNICAL SPECIFICATIONS:
Click Printable Version (PDF) for more information.