Mersen Home Page
 

<< Product Guide >>

Bolt-In Series A055B Product Page
 
Current Limiting Amp-Trap E-Rated

Amp-trap 5kV Bolt-in Series E-rated fuses are single, double or triple barrel (3" diam.) with end mounts designed for bolting directly to equipment bus or terminal pads. They are UL listed and are for use indoors (or outdoors in a weatherproof enclosure). The unique time-current characteristic of Mersen E-rated fuses allows them to be closely sized to transformer full load rated current, as recommended by IEEE guidelines, without being affected by normal magnetizing inrush current. Bolt-in fuses are typically sized at transformer rated current of 133%, thereby providing superior overall protection.

Features:
  • UL Listed for compatibility with UL listed equipment
  • Bolt-in mounting for direct connection to bus or terminals
  • Current Limiting for superior equipment protection
  • Blown-fuse indicator gives positive identification of open fuse
  • Non-venting for silent operation
  • Metal Embossed Catalog Number and manufacturing date for lasting identification
  • E-rated fuses operate as follows: 100E or less - must melt in 300 seconds (5 mins) at 200 to 240% of E (ampere) rating

  • Over 100E - must melt in 600 seconds (10 mins) at 220 to 264% of E (ampere) rating Example - A 100E fuse must melt in 300 seconds with an applied current of 200 to 240 amperes
  • General Purpose Current-Limiting Fuse: A general purpose current-limiting power fuse is one that is capable of interrupting all currents from its rated interrupting rating down to the current that causes melting of the fusible element in one hour
Ratings: 10E-900E / 5.5kV
Approvals: UL

E12E12
Items from this catalogue section:
 

Part Number

Description

A055B1DAR0-10E 5.5KV 3 DIA BOLT IN 10A
A055B1DAR0-15E 5.5KV 3 DIA BOLT IN 15A
A055B1DAR0-20E 5.5KV 3 DIA BOLT IN 20A
A055B1DAR0-25E 5.5KV 3 DIA BOLT IN 25A
A055B1DAR0-30E 5.5KV 3 DIA BOLT IN 30A
A055B1DAR0-40E 5.5KV 3 DIA BOLT IN 40A
A055B1DAR0-50E 5.5KV 3 DIA BOLT IN 50A
A055B1DAR0-65E 5.5KV 3 DIA BOLT IN 65A
A055B1DAR0-80E 5.5KV 3 DIA BOLT IN 80A
A055B1DAR0-100E 5.5KV 3 DIA BOLT IN 100A
A055B1DAR0-125E 5.5KV 3 DIA BOLT IN 125A
A055B1DAR0-150E 5.5KV 3 DIA BOLT IN 150A
A055B1DAR0-175E 5.5KV 3 DIA BOLT IN 175A
A055B1DAR0-200E 5.5KV 3 DIA BOLT IN 200A
A055B2DAR0-250E 80524-FUSE,MED VOLT 250A S221966
A055B2DAR0-300E 80525-FUSE,MED VOLT 300A B222710
A055B2DAR0-350E 80526-FUSE,MED VOLT 350A F201048
A055B2DAR0-400E 80527-FUSE,MED VOLT 400A P201562
A055B2DAR0-450E 80528-FUSE,MED VOLT 450A W212332
A055B2D0R0-450E 5.5KV 450E E-RATED BOLT-IN 450A
A055B2D0R0-500E 5.5KV 500E E-RATED BOLT-IN 500A
A055B2D0R0-600E 5.5KV 600E E-RATED BOLT-IN 600A
A055B3D0R0-750E 5.5KV 750E E RATED BOLT-IN 750A K212851
A055B3D0R0-900E 5.5KV 900E E RATED BOLT-IN 900A T213365
A050B4D0R0-1200E
9F62KCB500
9F62KCB600
9F62KCB700
9F62KCB800
9F62KCB900
A072B2D0R0-250E
A072B2D0R0-300E
A072B2D0R0-350E
A072B2D0R0-400E
A083B2DAR0-125E
A083B2DAR0-150E
A083B2DAR0-175E
A083B2DAR0-200E
A155B2D0R0-200E
A155B3D0R0-300E