Approvals & Standards
IEC 60282-1
Key features & benefits
Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear and controlgear and high-voltage systems for decades.
Limitor®-PD HV fuses are back-up fuses as defined in the standards: IEC 60282-1 and VDE 0670 T402 and dedicated to protect transformers against effects of short-circuit currents.
The VDE 0670 T402 defines fuses between 6.3A and 160A, for other ratings, thanks to consult Limitor®-P HV fuses range.
To guarantee high quality, Mersen uses the best materials: fuse-elements are in pure silver, caps are in copper coated with silver and bodies are in ceramic.
Applications
HV Transformer protection
Documents & Resources
Datasheet
Compliance
Item Number
B1000248
Catalog number
45DB120V80PD
Description
High Voltage DIN Back-up fuse for Transformer Limitor® VDE T402 12kVAC IEC 80A d65mm, L292mm With Striker 80N
EAN/UPC code
3605340456370
Rated voltage AC IEC
12 kV
Rated current
80 A
Fuse size
d=65mm, L=292mm
Mounting
Clip
Clearing I2t At Rated Voltage
87 kA²s
AC Max I.R./Breaking Capacity: I1
80 kA
Minimum breaking capacitiy (MBC)
345 A
Power Dissipation at Rated Current Value
82 W
Indication System
Yes
Indication System Type
Striker
Contact materials
Silver-Plated Copper
Connection/Terminal Type
Cylindrical
Body/Insulating Material
Ceramic
Product Weight
2.2 kg
Product Diameter
65 mm
Product Length
358 mm
Sell Pack Quantity
1 EACH
Sell Pack Weight
2.2 kg
Sell Pack Width
67 mm
Sell Pack Length
67 mm
Sell Pack Height
390 mm