NORMES
CARACTÉRISTIQUES ET AVANTAGES
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements.
MULTIVERT® 160A 60mm triple pole switching are for installation on to 60 mm bus bar systems.
MULTIVERT® 160A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 00: 160A.
The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
Applications
Documents & Ressources
Fiches techniques
Compliance
Numéro d'article
D1023158
Numéro de catalogue
1.003.308
Description
Interrupteur-sectionneur à fusible NH MULTIVERT® Taille 00 160A 1x3 pôles/coupure Système bus bar 60mm Bride de serrage / Vis raccord. haut prêt pr SF
Code EAN / UPC
9008567007990
Fréquence
50 ... 60 Hz
Tension nominale AC CEI
690 V
Courant assigné
160 A
Catégorie d'utilisation
AC 23 B @ Ue = AC 400 V; Ie = 160 A
Catégorie d'utilisation
AC 22 B @ Ue = AC 500 V; Ie = 160 A
Catégorie d'utilisation
AC 22 B @ Ue = AC 690 V; Ie = 100 A
Catégorie d'utilisation
DC 21 B @ Ue = DC 220 V; Ie = 160 A
Catégorie d'utilisation
DC 21 B @ Ue = DC 440 V; Ie = 100 A
Commutabilité
1 x triple pole
Conforme à ROHS
Oui
Courant nominal de court-circuit (SCCR)
120kA@Ue = AC 400 V; Ie = 160 A / 120kA@Ue = AC 500 V; Ie = 160 A / 50kA@Ue = AC 690 V; Ie = 100 A
Taille du fusible
00
Détails de conception
top terminal MULTIVERT® 1.003.307 with cabling of instrument leads
Nombre de pôles
3-Pole
Degré de pollution
3
Pouvoir assigné
uninterrupted duty
Tension nominale de tenue aux impulsions
8 kV
Tension d'isolation nominale
1000 V
Tenue au courant de circuit nominal
4.5 kA / 1 s
Courant thermique conventionnel en convection naturelle avec fusibles Ith
160 A
Courant thermique conventionnel à l'air libre - Parties solides
250 A
Dissipation maximale des parties fusibles Pn
12 W
Dissipation maximale des parties solides Pn
1.2 W
Dissipation à Ith sans fusibles
18 W
Dissipation thermique par Ith sans parties solides
44 W
Capacité nominale de court-circuit avec les parties solides Icm
4.5 kA
Installation de montage
Bus bar system 60 mm
Commentaires
Cable termination components : 3 M8 terminal screws/3 clamp straps 4-70 mm²
Poids du produit
1.5 kg
Largeur du produit
50.00 mm
Longueur du produit
116.00 mm
Hauteur du produit
406.00 mm
Quantité du pack de vente
1 EACH
Poids du pack de vente
1.5 kg
Largeur du pack de vente
130.00 mm
Longueur du pack de vente
440.00 mm
Hauteur du pack de vente
51.00 mm