Aller au contenu principal

All locations

Please select your country & language

China | 中国
Germany | Deutschland

Your country is not in the list?

Go to our international website:

Mersen EP International Website
Contactez-nous

NORMES

EN 60269-2 section II

CARACTÉRISTIQUES ET AVANTAGES

The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” protection (gG type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.

Plus de caractéristiques

Applications

  • These fuses are designed for : “General purpose use” protection (gG type)

Caractéristiques produit

Numéro d'article

E1019203  

Numéro de catalogue

BTC42V125  

Description

Fusible standard britannique CEI BS88 gG Type B1 415VAC 240VDC 125A BTC Boulonnés  

Code EAN / UPC

3605340515688  

Tension nominale AC CEI

415   V

Tension nominale DC CEI

240   V

Courant assigné

125   A

Vitesse/Caractéristique

gG  

Montage

Bolted  

I2t de coupure à tension nominale

78400   A²s

I2t de fusion

28000   A²s

Pouvoir de coupure maximal AC : I1

80   kA

Dissipation au courant nominal

11.3   W

Connexion / Matériel terminal

Tin-Plated Copper  

Type de Connexion / Borne

Slotted Blades  

Poids du produit

0.1245   kg

Diamètre du produit

26.9   mm

Largeur du produit

0   mm

Longueur du produit

137   mm

Quantité du pack de vente

10   EACH

Poids du pack de vente

1.245   kg

Largeur du pack de vente

145   mm

Longueur du pack de vente

150   mm

Hauteur du pack de vente

60   mm