NORMES
CARACTÉRISTIQUES ET AVANTAGES
The NH system is classified among plug-in fuse systems and is composed of:
Type "gG" NH fuse-links are full range breaking capacity fuse-links and are used to protect cables and equipment. They can interrupt any current surge, from the lowest fusing current up to their breaking capacity, and so can be used alone as protection. They also protect electrical devices and industrial set-ups from the electrodynamic effects of very high short-circuit currents.
Plus de caractéristiquesApplications
Documents & Ressources
Fiches techniques
Compliance
Numéro d'article
V233261
Numéro de catalogue
NH1GG69V224
Description
Cartouche fusible standard DIN NH gG Taille NH1 690VAC 400VDC 224A pattes non isolées Double indicateur Largeur du corps 40 mm
Code EAN / UPC
8430399026107
Tension nominale AC CEI
690 V
Tension nominale DC CEI
400 V
Courant assigné
224 A
Conforme à ROHS
Oui
Vitesse/Caractéristique
gG
Taille du fusible
NH1
Montage
Clip
Dissipation au courant nominal
19 W
Système d'indication
Oui
Type de système d'indication
Double Indicator Visual Indicator
Connexion / Matériel terminal
Silver-Plated Copper
Matériau isolant / corps
Ceramic
Poids du produit
0.42 kg
Largeur du produit
40 mm
Longueur du produit
135 mm
Hauteur du produit
64 mm
Quantité du pack de vente
3 EACH
Poids du pack de vente
1.26 kg
Largeur du pack de vente
125 mm
Longueur du pack de vente
139 mm
Hauteur du pack de vente
70 mm