Approvals & Standards
Key features & benefits
Amp-Trap 2000 time-delay A2D-R fuses provide IEC Type 2 "no damage" protection to existing mains, feeders, and branch circuits serving motor and non-motor loads. A2D-R fuses will open fast enough under extreme fault conditions for maximum short circuit protection to prevent damage to motor starters, switches, and other circuit components, yet also provide the time-delay needed for motor in-rush currents. A2D-R fuses can be used to replace older 250V Class H, K or RK5 fuses already installed in the field.
More specificationsApplications
Documents & Resources
Datasheet
Drawings
Curves
Compliance
Item Number
A2D35RN
Description
Fuse A2D-R - Class RK1 - Time-Delay 250VAC 250VDC 35A Ferrule Amp-Trap 2000®
EAN/UPC code
0782001504564
Rated voltage AC UL
250 V
Rated voltage DC UL
250 V
Frequency
50/60 Hz
Rated current
35 A
ROHS Compliant
Yes
AC or DC
AC/DC
Fuse class
Class RK1
Speed/Characteristic
Time Delay
Mounting
Clip
AC Max I.R./Breaking Capacity: I1
200 kA
Indication System
Yes
Indication System Type
SmartSpot®
Contact materials
Tin-Plated Copper
Connection/Terminal Type
Ferrule
Body/Insulating Material
PolyTube
Product Weight
0.054 kg
Product Diameter
20.6 mm
Product Length
76.2 mm
Sell Pack Quantity
10 EA
Sell Pack Weight
0.567 kg
Sell Pack Width
79.2 mm
Sell Pack Length
108 mm
Sell Pack Height
42.9 mm