Approvals & Standards
Key features & benefits
FR-type fuses are designed to protect HV/LV power distribution transformers. Designed to be coordinated with other equipment, these current limiting fuse-links interrupt fault currents before they reach their peak. The fault current is interrupted inside the fuse-link body and although this is very fast, there is no sign of it outside.
The 24kV fuses were specially designed with very low power losses, for use in SF6-insulated or compact air-insulated fused switchgear combinations
The main elements in these fuses are: a barrel of class F insulating synthetic material, nickel plated aluminium end contacts, pure silver fuse elements and a composite material fuse element holder to withstand high temperatures.
Thanks to their structure, based on a synthetic material, FR fuse-links are the perfect answer to the stress involved in use inside HV bays and fuse-link chambers.
Applications
Documents & Resources
Datasheet
Compliance
Item Number
Z227584
Catalog number
FR72V6,3
Description
High Voltage UTE Back-up fuse Limitor® 7.2kVAC IEC 6.3A d55mm, L520mm
EAN/UPC code
3605340275476
Rated voltage AC IEC
7.2 kV
Rated current
6.3 A
Fuse size
d=55mm, L=520mm
Mounting
Clip
Clearing I2t At Rated Voltage
0.3 kA²s
AC Max I.R./Breaking Capacity: I1
12.5 kA
Minimum breaking capacitiy (MBC)
31.5 A
Power Dissipation at Rated Current Value
12 W
Contact materials
Nickel-Plated Aluminum
Connection/Terminal Type
Cylindrical
Body/Insulating Material
Class F insulating synthetic material
Product Weight
2.1 kg
Product Diameter
55 mm
Product Length
520 mm
Sell Pack Quantity
3 EACH
Sell Pack Weight
6.3 kg
Sell Pack Width
270 mm
Sell Pack Length
670 mm
Sell Pack Height
100 mm