Approvals & Standards
Key features & benefits
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements.
MULTIVERT® 400A are for installation on to 185mm bus bar systems.
MULTIVERT® 400A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 2: 400A.
The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
2 alternative designs are available for a user-friendly and adaptable installation according to the needs:
- The standard design offers a very compact solution with an installation depth of only 123mm, enabling to save space in the Power distribution cabinets
- The i-Xtensio design offers a user-friendly mounting solution for current transformers at the back of the Multivert and more standard installation depth of 150mm
Applications
Documents & Resources
Datasheet
Compliance
Brochures
Frequency (Hz)
50 ... 60 Hz
Short Circuit Current Rating (SCCR)
120kA@Ue = AC 400 V; Ie = 400 A / 120kA@Ue = AC 500 V; Ie = 400 A / 120kA@Ue = AC 690 V; Ie = 315 A / 100kA@Ue = AC 690 V; Ie = 400 A
Degree of Protection (IP)
IP30
CE Conformity
Yes
REACH Compliant
Yes
A1023201 - 1.220.000
B1023202 - 1.220.900
C1023203 - 1.200.064
D1023204 - 1.200.074
E1023205 - 1.200.084
F1023206 - 1.200.094
G1023207 - 1.260.000
H1023208 - 1.270.000
J1002187 - 1.200.000
J1023209 - 1.270.100
K1023210 - 1.270.600
L1023211 - 1.270.900
M1002190 - 1.250.000
M1023212 - 1.250.064
N1023213 - 1.250.074