Skip to main content

All locations

Please select your country & language

China | 中国
Germany | Deutschland

Your country is not in the list?

Go to our international website:

Mersen EP International Website
Country / Language:  Canada / English
Contact us

Approvals & Standards

  • VDE 0636 Part 201
  • IEC 60269-1 and -2

Key features & benefits

The NH system is classified among plug-in fuse systems and is composed of:

  • fuse-base, (possibly including terminal covers and phase barriers)
  • fuse-link with blade contact
  • fuse-link replacement device (LV HRC fuse puller)
Since the design of this system cannot guarantee non-interchangeability of rated current, it must be handled by a qualified professional.

NH-fuse links „gTr“ are used for the protection of transformers. The time/current characteristic is especially adapted to that of the protected transformer and implies optimal selectivity to NH-fuse links characteristic gG. The fuses can be loaded with 1,3 times nominal current for up to 10 hours. The fuse link operates at 1,5 times nominal transformer current within 2 hours.

More specifications

Applications

  • Protection of transformers

Product Specifications

Ampere range

72 ... 1443 A  

Speed/Characteristic

gTr  

CE Conformity

Yes  

REACH Compliant

Yes  

References in this series  (33)

A1028698 - NH2GTR75KVA-8

108   A

NH2  

-

Yes  

0.5   kg

B1028699 - NH2GTR100KVA-8

144   A

NH2  

-

Yes  

0.5   kg

B1029067 - NH42GR1000KVA-8

1443   A

NH4a  

-

Yes  

2.2   kg

D1028701 - NH2GTR125KVA-8

180   A

NH2  

-

Yes  

0.5   kg

E1028702 - NH2GTR160KVA-8

231   A

NH2  

-

Yes  

0.5   kg

E1028725 - NH4AGTR100KVA-8

144   A

NH4a  

-

Yes  

2.2   kg

F1028703 - NH22GTR200KVA-8

289   A

NH2  

-

Yes  

0.5   kg

F1028726 - NH4AGTR125KVA-8

180   A

NH4a  

-

Yes  

2.2   kg

G1028704 - NH22GTR250KVA-8

361   A

NH2  

-

Yes  

0.5   kg

G1028727 - NH4AGTR160KVA-8

231   A

NH4a  

-

Yes  

2.2   kg

H1028728 - NH4AGTR200KVA-8

289   A

NH4a  

-

Yes  

2.2   kg

J1028729 - NH4AGTR250KVA-8

361   A

NH4a  

-

Yes  

2.2   kg

K1028707A - NH3GTR50KVA-8

72   A

NH3  

-

Yes  

1   kg

K1028730 - NH4AGTR315KVA-8

455   A

NH4a  

-

Yes  

2.2   kg

K1030110A - NH32GTR50KVA-8

72   A

NH3  

-

Yes  

1   kg